Table 729:
IEC Inverse time characteristics
Function
Range or value
Accuracy
Operating characteristic:
(
)
=
×
-
æ
ö
ç
÷
ç
÷
è
ø
1
P
A
t
td
I
EQUATION1653 V1 EN
I = I
measured
/I
set
td = (0.05-999) in steps of 0.01
-
Time delay to reset, IEC inverse time
(0.000-60.000) s
± 0.5% of set time ± 10
ms
IEC Normal Inverse
A=0.14, P=0.02
IEC 60255-151, 5% + 40
ms
IEC Very inverse
A=13.5, P=1.0
IEC Inverse
A=0.14, P=0.02
IEC Extremely inverse
A=80.0, P=2.0
IEC Short time inverse
A=0.05, P=0.04
IEC Long time inverse
A=120, P=1.0
Programmable characteristic
Operate characteristic:
(
)
=
+
×
-
æ
ö
ç
÷
ç
÷
è
ø
P
A
t
B
td
I
C
EQUATION1654 V1 EN
Reset characteristic:
(
)
=
×
-
PR
TR
t
td
I
CR
EQUATION1655 V1 EN
I = I
measured
/I
set
td = (0.05-999) in steps of 0.01
A=(0.005-200.000) in steps of
0.001
B=(0.00-20.00) in steps of 0.01
C=(0.1-10.0) in steps of 0.1
P=(0.005-3.000) in steps of 0.001
TR=(0.005-100.000) in steps of
0.001
CR=(0.1-10.0) in steps of 0.1
PR=(0.005-3.000) in steps of
0.001
1MRK505222-UUS C
Section 22
Inverse time characteristics
1189
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...