Name
Type
Description
VPS1S2TR
BOOLEAN
Status of the apparatuses between bus section 1 and
2 are valid
VPQB1TR
BOOLEAN
Switch status of 189 is valid (open or closed)
VPQB2TR
BOOLEAN
Switch status of 289 is valid (open or closed)
12.4.6
Interlocking for bus-section disconnector A1A2_DC (3)
12.4.6.1
Introduction
The interlocking for bus-section disconnector (A1A2_DC, 3) function is used for one
bus-section disconnector between section 1 and 2 according to figure
. A1A2_DC (3)
function can be used for different busbars, which includes a bus-section disconnector.
WA1 (A1)
WA2 (A2)
189G
289G
A1A2_DC
en04000492_ansi.vsd
52
ANSI04000492 V1 EN
Figure 361:
Switchyard layout A1A2_DC (3)
12.4.6.2
Function block
ANSI05000349-2-en.vsd
A1A2_DC (3)
089_OP
089_CL
S189G_OP
S189G_CL
S289G_OP
S289G_CL
S1DC_OP
S2DC_OP
VPS1_DC
VPS2_DC
EXDU_89G
EXDU_BB
089C_EX1
089C_EX2
089O_EX1
089O_EX2
089O_EX3
089OPREL
089OPITL
089CLREL
089CLITL
DCOPTR
DCCLTR
VPDCTR
ANSI05000349 V2 EN
Figure 362:
A1A2_DC (3) function block
Section 12
1MRK505222-UUS C
Control
702
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...