13.6.5
Setting parameters
Table 442:
ECRWPSCH (85) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CurrRev
Disabled
Enabled
-
-
Disabled
Operating mode of Current Reversal Logic
tPickUpRev
0.000 - 60.000
s
0.001
0.020
Pickup time for current reversal logic
tDelayRev
0.000 - 60.000
s
0.001
0.060
Time Delay to prevent Carrier send and local
trip
WEI
Disabled
Echo
Echo & Trip
-
-
Disabled
Operating mode of WEI logic
tPickUpWEI
0.000 - 60.000
s
0.001
0.000
Coordination time for the WEI logic
VBase
0.05 - 2000.00
kV
0.05
400.00
Base setting for voltage level
3V0PU
5 - 70
%VB
1
25
Neutral voltage setting for fault conditions
measurement
13.6.6
Technical data
Table 443:
ECRWPSCH (85) technical data
Function
Range or value
Accuracy
Operating mode of WEI logic
Disabled
Echo
Echo & Trip
-
Operate voltage 3V
o
for WEI trip
(5-70)% of VBase
± 0.5% of Vn
Reset ratio
>95%
-
Operate time for current reversal
logic
(0.000-60.000) s
± 0.5% ± 10 ms
Delay time for current reversal
(0.000-60.000) s
± 0.5% ± 10 ms
Coordination time for weak-end
infeed logic
(0.000–60.000) s
± 0.5% ± 10 ms
13.7
Current reversal and weak-end infeed logic for phase
segregated communication ZC1WPSCH (85)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for phase segregated
communication
ZC1WPSCH
-
85
Section 13
1MRK505222-UUS C
Scheme communication
822
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...