Name
Values (Range)
Unit
Step
Default
Description
PhaseDiffA
5.0 - 90.0
Deg
1.0
25.0
Phase angle difference limit between bus and
line Auto
PhaseDiffM
5.0 - 90.0
Deg
1.0
25.0
Phase angle difference limit between bus and
line Manual
tSCA
0.000 - 60.000
s
0.001
0.100
Time delay output for synchrocheck Auto
tSCM
0.000 - 60.000
s
0.001
0.100
Time delay output for synchrocheck Manual
AutoEnerg
Disabled
DLLB
DBLL
Both
-
-
DBLL
Automatic energizing check mode
ManEnerg
Disabled
DLLB
DBLL
Both
-
-
Both
Manual energizing check mode
ManEnergDBDL
Disabled
Enabled
-
-
Disabled
Manual dead bus, dead line energizing
VLiveBusEnerg
50.0 - 120.0
%VBB
1.0
80.0
Voltage high limit bus for energizing check in
% of UBaseBus
VLiveLineEnerg
50.0 - 120.0
%VBL
1.0
80.0
Voltage high limit line for energizing check in
% of VBaseLine
VDeadBusEnerg
10.0 - 80.0
%VBB
1.0
40.0
Voltage low limit bus for energizing check in
% of VBaseBus
VDeadLineEnerg
10.0 - 80.0
%VBL
1.0
40.0
Voltage low limit line for energizing check in
% of VBaseLine
VMaxEnerg
50.0 - 180.0
%VB
1.0
115.0
Maximum voltage for energizing in % of
VBase, Line and/or Bus
tAutoEnerg
0.000 - 60.000
s
0.001
0.100
Time delay for automatic energizing check
tManEnerg
0.000 - 60.000
s
0.001
0.100
Time delay for manual energizing check
Section 12
1MRK505222-UUS C
Control
630
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...