Current variation
subfunction
I3P
t
ANSI10000295-1-en.vsd
t
t
Pick Up VAB
Pick Up VBC
Pick Up VCA
STCV
OR
Time Delay CV
cont
cont
Time Delay CV
Time Delay CV
i
ANSI10000295 V1 EN
Figure 67:
Current variation logic diagram
Time Delay CV
is the time setting for the change of current criterion. Phase current
samples are included in input signal I3P.
Zero sequence current criterion
Zero sequence criterion is mainly for detection of remote IED high resistance faults or
some gradual faults. The criterion takes the zero sequence current as input. Zero
sequence current is compared with
PU 3I0
for the
t3I0
time to generate the zero
sequence current startup signal.
a>b
a
b
AND
PU 3I0
BLK3I0
BLOCK
Pick Up 3I0
I3P
OR
t
t3I0
ANSI09000778-2-en.vsd
ANSI09000778 V2 EN
Figure 68:
Zero sequence current criterion logic diagram
Here
PU 3I0
is the setting of the maximum possible non-faulted zero sequence current
for the protected line. The default value for this setting is 0.1 ·
IBase
where
IBase
is the
rated current of the CT.
t3I0
is the time setting for the zero sequence current criterion.
1MRK505222-UUS C
Section 5
Differential protection
167
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...