Name
Values (Range)
Unit
Step
Default
Description
R0PG
0.50 - 3000.00
ohm/p
0.01
5.00
Zero seq. resistance for zone characteristic
angle, Ph-G
RFltFwdPP
0.50 - 3000.00
ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, forward
RFltRevPP
0.50 - 3000.00
ohm/l
0.01
30.00
Fault resistance reach, Ph-Ph, reverse
RFltFwdPG
1.00 - 9000.00
ohm/l
0.01
100.00
Fault resistance reach, Ph-G, forward
RFltRevPG
1.00 - 9000.00
ohm/l
0.01
100.00
Fault resistance reach, Ph-G, reverse
IMinPUPP
5 - 500
%IB
1
10
Minimum pickup delta current (2 x current of
lagging phase) for Phase-to-phase loops
IMinPUPG
5 - 500
%IB
1
5
Minimum pickup phase current for Phase-to-
ground loops
Table 159:
FRPSPDIS (21) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TimerPP
Disabled
Enabled
-
-
Disabled
Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP
0.000 - 60.000
s
0.001
3.000
Time delay to trip, Ph-Ph
TimerPE
Disabled
Enabled
-
-
Disabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
tPG
0.000 - 60.000
s
0.001
3.000
Time delay to trip, Ph-E
6.10.6
Technical data
Table 160:
FRPSPDIS (21) technical data
Function
Range or value
Accuracy
Minimum operate current
(5-500)% of IBase
-
Reactive reach, positive
sequence
(0.50–3000.00) Ω/phase
± 2.0% static accuracy
± 2.0 degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x I
n
Current range: (0.5-30) x IBase
Angle: at 0 degrees and 85
degrees
Resistive reach, positive
sequence
(0.10–1000.00) Ω/phase
Reactive reach, zero sequence
(0.50–9000.00) Ω/phase
Resistive reach, zero sequence
(0.50–3000.00) Ω/phase
Fault resistance, phase-to-
ground faults, forward and
reverse
(1.00–9000.00) Ω/loop
Fault resistance, phase-to-
phase faults, forward and reverse
(0.50–3000.00) Ω/loop
Load encroachment criteria:
Load resistance, forward and
reverse
Safety load impedance angle
(1.00–3000.00) Ω/phase
(5-70) degrees
Reset ratio
105% typically
-
Section 6
1MRK505222-UUS C
Impedance protection
346
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...