Table 144:
FMPSPDIS Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
DeltaIMinOp
5 - 100
%IB
1
10
Delta current level in % of IBase
DeltaVMinOp
5 - 100
%VB
1
20
Delta voltage level in % of Vbase
V1Level
5 - 100
%VB
1
80
Pos seq voltage limit for identification of 3-ph
fault
I1LowLevel
5 - 200
%IB
1
10
Pos seq current level for identification of 3-ph
fault in % of IBase
V1MinOp
5 - 100
%VB
1
20
Minimum operate positive sequence voltage
for ph sel
V2MinOp
1 - 100
%VB
1
5
Minimum operate negative sequence voltage
for ph sel
INRelPG
10 - 100
%IB
1
20
3I0 limit for release ph-g measuring loops in
% of max phase current
3I0BLK_PP
10 - 100
%IB
1
40
3I0 limit for blocking phase-to-phase
measuring loops in % of max phase current
6.8.6
Technical data
Table 145:
FMPSPDIS (21) technical data
Function
Range or value
Accuracy
Minimum operate current
(5-30)% of
IBase
± 1.0% of I
n
Load encroachment criteria:
Load resistance, forward and
reverse
(0.5–3000)
W
/phase
(5–70) degrees
± 2.0% static accuracy
Conditions:
Voltage range: (0.1–1.1) x V
n
Current range: (0.5–30) x I
n
Angle: at 0 degrees and 85 degrees
6.9
Distance protection zone, quadrilateral characteristic,
separate settings ZMRPDIS (21), ZMRAPDIS (21)
and ZDRDIR (21D)
1MRK505222-UUS C
Section 6
Impedance protection
303
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...