13.2
Phase segregated scheme communication logic for
distance protection ZC1PPSCH (85)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Phase segregated Scheme
communication logic for distance
protection
ZC1PPSCH
-
85
13.2.1
Introduction
Communication between line ends is used to achieve fault clearance for all faults on a
power line. All possible types of communication schemes for example, permissive
underreach, permissive overreach and blocking schemes are available. To manage
problems with simultaneous faults on parallel power lines phase segregated
communication is needed. This will then replace the standard Scheme communication
logic for distance or Overcurrent protection (ZCPSCH, 85) on important lines where
three communication channels (in each subsystem) are available for the distance
protection communication.
The main purpose of the Phase segregated scheme communication logic for distance
protection (ZC1PPSCH, 85) function is to supplement the distance protection function
such that:
•
fast clearance of faults is also achieved at the line end for which the faults are on
the part of the line not covered by its underreaching zone.
•
correct phase selection can be maintained to support single-pole tripping for faults
occurring anywhere on the entire length of a double circuit line.
To accomplish this, three separate communication channels, that is, one per phase,
each capable of transmitting a signal in each direction is required.
ZC1PPSCH (85) can be completed with the current reversal and WEI logic for phase
segregated communication, when found necessary in Blocking and Permissive
overreaching schemes.
13.2.2
Principle of operation
Depending on whether a reverse or forward directed impedance zone is used to issue
the send signal, the communication schemes are divided into Blocking and Permissive
schemes, respectively.
Section 13
1MRK505222-UUS C
Scheme communication
796
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...