Information number is defined for output signals.
Ground fault indications in monitor direction, I103EF
Indication block for ground fault in monitor direction with defined functions.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signal.
Info. no.
Message
Supported
48
Ground fault A
No
49
Ground fault B
No
50
Ground fault C
No
51
Ground fault forward
Yes
52
Ground fault reverse
Yes
Fault indications in monitor direction, type 1, I103FltDis
Fault indication block for faults in monitor direction with defined functions.
The instance type is suitable for distance protection function.
FUNCTION TYPE parameter for each block.
INFORMATION NUMBER is defined for each input signal.
Number of instances: 1
Info. no.
Message
Supported
64
Start L1
Yes
65
Start L2
Yes
66
Start L3
Yes
67
Start IN
Yes
84
General start
Yes
69
Trip L1
Yes
70
Trip L2
Yes
71
Trip L3
Yes
68
General trip
Yes
74
Fault forward/line
Yes
75
Fault reverse/busbar
Yes
78
Zone 1
Yes
Table continues on next page
Section 17
1MRK505222-UUS C
Station communication
1040
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...