The type A curve is described as:
TD
t
Vpickup
V
Vpickup
=
< -
<
ANSIEQUATION1431 V1 EN
(Equation 119)
where:
Vpickup
<
Set value for step 1 and step 2
V
Measured voltage
The type B curve is described as:
2.0
480
0.055
Vpickup < -V
32
0.5
Vpickup
TD
t
×
=
+
×
-
<
æ
ö
ç
÷
è
ø
EQUATION1608 V1 EN
(Equation 120)
The customer programmable curve can be created as:
P
TD A
t
D
Vpickup
V
B
C
Vpickup
×
=
+
< -
×
-
é
ù
ê
ú
ê
ú
ê
ú
æ
ö
ê
ú
ç
÷
è
ø
ë
û
EQUATION1609 V1 EN
(Equation 121)
When the denominator in the expression is equal to zero the time delay will be infinity.
There will be an undesired discontinuity. Therefore a tuning parameter
CrvSatn
is set
to compensate for this phenomenon. In the voltage interval
Vpickup<
down to
Vpickup<
· (1.0 –
CrvSatn/
100) the used voltage will be:
Vpickup<
· (1.0 –
CrvSatn
/
100). If the programmable curve is used this parameter must be calculated so that:
0
100
CrvSatn
B
C
×
- >
EQUATION1435 V1 EN
(Equation 122)
1MRK505222-UUS C
Section 8
Voltage protection
493
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...