6.15.4
Input and output signals
Table 180:
PPLPHIZ Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for current input
V3P
GROUP
SIGNAL
-
Group signal for voltage input
BLOCK
BOOLEAN
0
Block of function
RELAG
BOOLEAN
0
Release condition for the A to ground loop
RELBG
BOOLEAN
0
Release condition for the B to ground loop
RELCG
BOOLEAN
0
Release condition for the C to ground loop
PHSEL
INTEGER
0
Integer coded external release signals
Table 181:
PPLPHIZ Output signals
Name
Type
Description
BFI_3P
BOOLEAN
Indicates start for ground fault(s), regardless of direction
ZREL
INTEGER
Integer coded output release signal
6.15.5
Setting parameters
Table 182:
PPLPHIZ Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
IBase
1 - 99999
A
1
3000
Base current
VBase
0.05 - 2000.00
kV
0.01
400.00
Base voltage
OperMode
No Filter
NoPref
1231c
1321c
123a
132a
213a
231a
312a
321a
-
-
No Filter
Operating mode (c=cyclic,a=acyclic)
PU27PN
10 - 100
%VB
1
70
Operate value of 27P in % of VBase/sqrt(3)
PU27PP
10 - 100
%VB
1
50
Pickup value of line to line undervoltage (% of
VBase)
3V0PU
5 - 300
%VB
1
20
Operate value of residual voltage in % VBase/
sqrt(3)
Pickup_N
10 - 200
%IB
1
20
Pickup value of residual current (% of IBase)
Table continues on next page
Section 6
1MRK505222-UUS C
Impedance protection
376
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...