After the first slip, the signals ZONE1 or ZONE2 and – depending on the direction of
slip - either GEN or MOTOR are issued.
Every time pole slipping is detected, the impedance of the point where the slip line is
crossed and the instantaneous slip frequency are displayed as measurements.
Further slips are only detected, if they are in the same direction and if the rate of rotor
movement has reduced in relation to the preceding slip or the slip line is crossed in the
opposite direction outside ZA-ZB. A further slip in the opposite direction within Z
A
-Z
B
resets all the signals and is then signalled itself as a first slip.
The TRIP1 tripping command and signal are generated after N1 slips in zone 1,
providing the rotor angle is less than
TripAngle
. The TRIP2 signal is generated after
N2 slips in zone 2, providing the rotor angle is less than
TripAngle
.
All signals are reset if:
•
the direction of movement reverses
•
the rotor angle detector resets without a slip being counted or
•
no rotor relative movement was detected during the time
ResetTime
.
Section 6
1MRK505222-UUS C
Impedance protection
364
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...