Features:
•
Phase wise pickup and trip signals
•
Overcurrent protection
•
Phase wise RMS current is available as service values
•
Single definite time stage trip function.
13.8.10.2
Principle of operation
Three phase overcurrent (LCP3PTOC, 51) is used for detecting over current
conditions. LCP3PTOC (51) pickups when the current exceeds the set limit
PU 51
. It
operates with definite time (DT) characteristics, that is, the function operates after a
predefined time
tOC
and resets when the fault current disappears. The function
contains a blocking functionality. It is possible to block the function output, timer or
the function itself, if desired.
13.8.10.3
Function block
ANSI09000771-1-en.vsd
LCP3PTOC (51)
I3P*
BLOCK
BLKTR
TRIP
TR_A
TR_B
TR_C
RI
PU_A
PU_B
BFI_C
ANSI09000771 V1 EN
Figure 425:
LCP3PTOC (51) Function block
13.8.10.4
Input and output signals
Table 483:
LCP3PTOC (51) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block all binary outputs by resetting timers
BLKTR
BOOLEAN
0
Block trip of the function
1MRK505222-UUS C
Section 13
Scheme communication
853
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...