ANSI09000209-1-en.vsd
Synchro
check
OR
SCSWI
SXCBR
CLOSE
SYNC_OK
EXE_CL
Synchronizing
function
SY_INPRO
START_SY
CLOSECMD
SESRSYN
ANSI09000209 V1 EN
Figure 331:
Example of interaction between SCSWI, SESRSYN (25) (synchronism
check and synchronizing function) and SXCBR function
Time diagrams
The Switch controller (SCSWI) function has timers for evaluating different time
supervision conditions. These timers are explained here.
The timer
tSelect
is used for supervising the time between the select and the execute
command signal, that is, the time the operator has to perform the command execution
after the selection of the object to operate.
select
tSelect
timer
execute command
t1
t1>tSelect, then long-
operation-time in 'cause'
is set
en05000092.vsd
IEC05000092 V1 EN
Figure 332:
tSelect
The parameter
tResResponse
is used to set the maximum allowed time to make the
reservation, that is, the time between reservation request and the feedback reservation
granted from all bays involved in the reservation function.
1MRK505222-UUS C
Section 12
Control
665
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...