7.7.6
Technical data
Table 218:
LFPTTR/LCPTTR (26) technical data
Function
Range or value
Accuracy
Reference current
(0-400)% of
IBase
±
1.0% of I
n
Reference temperature
(0-400)°C, (0 - 600)°F
±
2°F, ±2°F
Trip time:
2
2
2
2
2
ln
p
Trip
Amb
p
ref
ref
I
I
t
T
T
I
I
I
T
t
-
=
-
-
-
×
é
ù
ê
ú
ê
ú
ê
ú
ê
ú
ë
û
EQUATION13000039 V2 EN
(Equation 96)
T
Trip
= set trip temperature
T
Amb
= ambient temperature
T
ref
= temperature rise above ambient at I
ref
I
ref
= reference load current
I = actual measured current
I
p
= load current before overload occurs
Time constant
t
= (1–1000) minutes IEC 60255-8, ±5.0%
or ±200 ms
whichever is greater
Alarm temperature
(0-400)°F, (0-200)°C
±
2.0% of heat
content trip
Trip temperature
(0-400)°C, (0-600)°F
±
2.0% of heat
content trip
Reset level temperature
(0-400)°C, (0-600)°F
±
2.0% of heat
content trip
7.8
Breaker failure protection CCRBRF (50BF)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Breaker failure protection
CCRBRF
3I>BF
SYMBOL-U V1 EN
50BF
Section 7
1MRK505222-UUS C
Current protection
456
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...