7.8.3
Function block
CCRBRF (50BF)
I3P*
BLOCK
BFI_3P
BFI_A
BFI_B
BFI_C
52A_A
52A_B
52A_C
52FAIL
TRBU
TRBU2
TRRET
TRRET_A
TRRET_B
TRRET_C
CBALARM
ANSI06000188-2-en.vsd
ANSI06000188 V2 EN
Figure 231:
CCRBRF (50BF) function block
7.8.4
Input and output signals
Table 219:
CCRBRF (50BF) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase group signal for current inputs
BLOCK
BOOLEAN
0
Block of function
BFI_3P
BOOLEAN
0
Three phase breaker failure initiation
BFI_A
BOOLEAN
0
Phase A breaker failure initiation
BFI_B
BOOLEAN
0
Phase B breaker failure initiation
BFI_C
BOOLEAN
0
Phase C breaker failure initiation
52a_A
BOOLEAN
1
Circuit breaker closed in phase A
52a_B
BOOLEAN
1
Circuit breaker closed in phase B
52a_C
BOOLEAN
1
Circuit breaker closed in phase C
52FAIL
BOOLEAN
0
CB faulty, unable to trip. Back-up trip instantaneously
Table 220:
CCRBRF (50BF) Output signals
Name
Type
Description
TRBU
BOOLEAN
Back-up trip by breaker failure protection function
TRBU2
BOOLEAN
Second back-up trip by breaker failure protection
function
TRRET
BOOLEAN
Retrip by breaker failure protection function
TRRET_A
BOOLEAN
Retrip by breaker failure protection function phase A
TRRET_B
BOOLEAN
Retrip by breaker failure protection function phase B
TRRET_C
BOOLEAN
Retrip by breaker failure protection function phase C
CBALARM
BOOLEAN
Alarm for faulty circuit breaker
Section 7
1MRK505222-UUS C
Current protection
460
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...