13.8.3.5
Setting parameters
Table 454:
COUVGAPC (59_27) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Enable/Disable
VBase
0.05 - 2000.00
kV
0.05
400.00
Base setting for voltage in kV
OperationUV
Disabled
Enabled
-
-
Enabled
Operation compensated under voltage Off/On
27_COMP
1 - 100
%VB
1
70
Compensated under voltage level in % of
VBase
tUV
0.000 - 60.000
s
0.001
1.000
Time delay to trip under voltage
OperationOV
Disabled
Enabled
-
-
Enabled
Operation compensated over voltage Off/On
59_COMP
1 - 200
%VB
1
120
Compensated over voltage level in % of VBase
tOV
0.000 - 60.000
s
0.001
5.000
Time delay to trip over voltage
Table 455:
COUVGAPC (59_27) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
HystAbs
0.0 - 100.0
%VB
0.1
0.5
Hysteresis absolute for compensated over/
under voltage in % of VBase
Section 13
1MRK505222-UUS C
Scheme communication
838
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...