AngleRCA
Forward
Area
Iop = I2
Vpol=-V2
Reverse
Area
ANSI10000031-1-en.vsd
ANSI10000031 V1 EN
Figure 214:
Operating characteristic for fault directional element
Two relevant setting parameters for directional supervision element are:
•
Directional element is internally enable to operate as soon as I
Op
is bigger than
40% of
INDirPU
and the directional condition is fulfilled in set direction.
•
Relay characteristic angle
AngleRCA
which defines the position of forward and
reverse areas in the operating characteristic.
Directional comparison step, built-in within directional supervision element, set
NS4PTOC (4612) output binary signals:
1. PUFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area,
see fig
(Operating quantity magnitude is bigger than setting
INDirPU
)
2. PUREV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse
area, see fig
. (Operating quantity magnitude is bigger than 60% of setting
INDirPU
)
1MRK505222-UUS C
Section 7
Current protection
427
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...