If the PUZMUR signal appears at the same time as the PUZMOR or if it appears
with a time delay, which is shorter than the time delay set on timer
tDZ
.
•
If the PUZMUR signal appears after the PUZMOR signal with a time delay longer
than the delay set on the
tDZ
timer, and remains active longer than the time delay
set on the
tZL
timer.
The functional output signal can be used to block the operation of the higher distance
protection zone, if the fault has moved into the zone 1 operate area after
tDZ
time delay.
6.12.3
Function block
ANSI07000026-2-en.vsd
ZMRPSL
BLOCK
PUZMUR
PUZMOR
PUPSD
PUDOG
PUZMPSD
PLTR_CRD
AR1P1
CSUR
CR
TRIP
PUZMURPS
BLKZMUR
BLKZMOR
CS
ANSI07000026 V2 EN
Figure 191:
ZMRPSL function block
6.12.4
Input and output signals
Table 166:
ZMRPSL Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
PUZMUR
BOOLEAN
0
Pickup of the underreaching zone
PUZMOR
BOOLEAN
0
Pickup of the overreaching zone
PUPSD
BOOLEAN
0
Power swing detected
PUDOG
BOOLEAN
0
Pickup from ground Fault Protection in forward or
reverse direction
PUZMPSD
BOOLEAN
0
Operation of Power Swing Detection external
characteristic
PLTR_CRD
BOOLEAN
0
Overreaching ZM zone to be accelerated
AR1P1
BOOLEAN
0
Single pole auto-reclosing in progress
CSUR
BOOLEAN
0
Carrier send by the underreaching power-swing zone
CR
BOOLEAN
0
Carrier receive signal during power swing detection
operation
1MRK505222-UUS C
Section 6
Impedance protection
359
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...