Because of limitations of space, when ring lug terminal is ordered for
Binary I/O connections, one blank slot is necessary between two
adjacent IO cards. Please refer to the ordering particulars for details.
19.5.3
Influencing factors
Table 720:
Temperature and humidity influence
Parameter
Reference value
Nominal range
Influence
Ambient temperature,
operate value
+20 °C
-10 °C to +55 °C
0.02% /°C
Relative humidity
Operative range
10%-90%
0%-95%
10%-90%
-
Storage temperature
-40 °C to +70 °C
-
-
Table 721:
Auxiliary DC supply voltage influence on functionality during operation
Dependence on
Reference value
Within nominal range Influence
Ripple, in DC auxiliary voltage
Operative range
max. 2%
Full wave rectified
15% of EL
0.01% /%
Auxiliary voltage dependence, operate
value
± 20% of EL
0.01% /%
Interrupted auxiliary DC voltage
24-60 V DC ± 20%
90-250 V DC
±
20%
Interruption
interval
0–50 ms
No restart
0–∞ s
Correct behaviour
at power down
Restart time
<300 s
Section 19
1MRK505222-UUS C
IED hardware
1154
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...