1. Residual current criteria, that is, separation of faults with and without ground
connection
2. Regular quadrilateral impedance characteristic
3. Load encroachment characteristics is always active but can be switched off by
selecting a high setting.
The current pickup condition DLECND is based on the following criteria:
1. Residual current criteria
2. No quadrilateral impedance characteristic. The impedance reach outside the load
area is theoretically infinite. The practical reach, however, will be determined by
the minimum operating current limits.
3. Load encroachment characteristic is always active, but can be switched off by
selecting a high setting.
The DLECND output is non-directional. The directionality is determined by the
distance zones directional function. There are outputs from FDPSPDIS (21) that
indicate whether a pickup is in forward or reverse direction or non-directional, for
example FWD_A, REV_A and NDIR_A.
These directional indications are based on the sector boundaries of the directional
function and the impedance setting of FDPSPDIS (21) function. Their operating
characteristics are illustrated in figure
.
en05000668_ansi.vsd
R
X
R
X
R
X
Non-directional (ND)
Forward (FWD)
Reverse (REV)
60°
60°
60°
60°
ANSI05000668 V1 EN
Figure 101:
Characteristics for non-directional, forward and reverse operation of
Phase selection with load encroachment, quadrilateral characteristic
FDPSPDIS (21)
Section 6
1MRK505222-UUS C
Impedance protection
220
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...