Function or quantity
Trip and Signal relays
Making capacity at inductive load with L/R>10 ms
0.2 s
1.0 s
30 A
10 A
Breaking capacity for AC, cos
j
>0.4
250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
Maximum 72 outputs may be activated simultaneously with influencing
factors within nominal range. After 6 ms an additional 24 outputs may
be activated. The activation time for the 96 outputs must not exceed
200 ms. 48 outputs can be activated during 1 s. Continued activation is
possible with respect to current consumption but after 5 minutes the
temperature rise will adversely affect the hardware life. Maximum two
relays per BOM/IOM/SOM should be activated continuously due to
power dissipation.
19.2.11
Static binary output module (SOM)
19.2.11.1
Introduction
The static binary output module has six fast static outputs and six change over output
relays for use in applications with high speed requirements.
19.2.11.2
Design
The Static output module (SOM) have 6 normally open (NO) static outputs and 6
electromechanical relay outputs with change over contacts.
The SOM consists mainly of:
•
An MCU
•
A CAN-driver
•
6 static relays outputs
•
6 electromechanical relay outputs
•
A DC/DC converter
•
Connectors interfacing
•
CAN-bus to backplane CBM
•
IO-connectors to binary outputs (2 pcs.)
Section 19
1MRK505222-UUS C
IED hardware
1106
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...