13.5.5
Setting parameters
Table 437:
ECPSCH (85) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
-
-
Permissive UR
Scheme type, Mode of Operation
tCoord
0.000 - 60.000
s
0.001
0.035
Communication scheme channel coordination
time
tSendMin
0.000 - 60.000
s
0.001
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Table 438:
ECPSCH (85) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Unblock
Disabled
NoRestart
Restart
-
-
Disabled
Operation mode of unblocking logic
tSecurity
0.000 - 60.000
s
0.001
0.035
Security timer for loss of carrier guard detection
13.5.6
Technical data
Table 439:
ECPSCH (85) technical data
Function
Range or value
Accuracy
Scheme type
Permissive Underreaching
Permissive Overreaching
Blocking
-
Communication scheme
coordination time
(0.000-60.000) s
± 0.5% ± 10 ms
13.6
Current reversal and weak-end infeed logic for
residual overcurrent protection ECRWPSCH (85)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Current reversal and weak-end infeed
logic for residual overcurrent protection
ECRWPSCH
-
85
1MRK505222-UUS C
Section 13
Scheme communication
817
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...