If the above criteria becomes true for a time of
tDelay
, then respective RI output is
activated provided the BLOCK input is false, and the respective TRIP outputs is
activated for the time of
tHold
provided the BLKTR and BLOCK input is false.
13.8.4.3
Function block
ANSI09000765-1-en.vsd
SCCVPTOC (51)
I3P*
BLOCK
BLKTR
TRIP
RI
ANSI09000765 V1 EN
Figure 419:
SCCVPTOC (51) function block
13.8.4.4
Input and output signals
Table 458:
SCCVPTOC (51) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Three phase to phase current samples group
BLOCK
BOOLEAN
0
Block of function
BLKTR
BOOLEAN
0
Block trip signals
Table 459:
SCCVPTOC (51) Output signals
Name
Type
Description
TRIP
BOOLEAN
Common trip signal
RI
BOOLEAN
Common start signal
13.8.4.5
Setting parameters
Table 460:
SCCVPTOC (51) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Off/On
IBase
1 - 99999
A
1
3000
Base setting for current in A
IPickup
0 - 100
%IB
1
20
Fixed threshold setting in % of IBase
tHold
0.000 - 60.000
s
0.001
0.500
Hold time for operate signals
1MRK505222-UUS C
Section 13
Scheme communication
841
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...