Quantity
Rated value
Nominal range
Burden
< 150 mVA at I
n
= 5 A
< 20 mVA at I
n
= 1 A
Ac voltage
V
n
= 120 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
< 20 mVA at 110 V
Frequency
f
n
= 60/50 Hz
± 5%
*)
max. 350 A for 1 s when COMBITEST test switch is included.
Table 693:
TRM - Energizing quantities, rated values and limits for measuring transformer modules
Quantity
Rated value
Nominal range
Current
I
n
= 1 or 5 A
(0-1.8) × I
n
at I
n
= 1 A
(0-1.6) × I
n
at I
n
= 5 A
Permissive overload
1.1 × I
n
cont.
1.8 × I
n
for 30 min at I
n
= 1 A
1.6 × I
n
for 30 min at I
n
= 5 A
Burden
< 350 mVA at I
n
= 5 A
< 200 mVA at I
n
= 1 A
Ac voltage
V
n
= 120 V
0.5–288 V
Operative range
(0–340) V
Permissive overload
420 V cont.
450 V 10 s
Burden
< 20 mVA at 110 V
Frequency
f
n
= 60/50 Hz
± 5%
19.2.8
Analog digital conversion module, with time synchronization
(ADM)
19.2.8.1
Introduction
The Analog/Digital module has twelve analog inputs, 2 PC-MIP slots and 1 PMC slot.
The PC-MIP slot is used for PC-MIP cards and the PMC slot for PMC cards according
to table
. The OEM card should always be mounted on the ADM board. The UBM
connects the ADM to the transformer input module (TRM).
Section 19
1MRK505222-UUS C
IED hardware
1096
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...