Function
Range or value
Accuracy
EndSection 2
(100–1000)% of
IBase
-
Unrestrained limit function
(100–5000)% of
IBase
± 1.0% of I
n
at I ≤ I
n
± 1.0% of I at I > I
n
Second harmonic blocking
(5.0–100.0)% of fundamental
± 2.0% of I
n
Fifth harmonic blocking
(5.0–100.0)% of fundamental
± 6.0% of I
n
Inverse characteristics, see table
,
19 curve types
and table
Operate time
25 ms typically at 0 to 10 x I
d
-
Reset time
15 ms typically at 10 to 0 x I
d
-
Critical impulse time
2 ms typically at 0 to 10 x I
d
-
Charging current compensation
On/Off
-
5.2
1Ph High impedance differential protection HZPDIF
(87)
5.2.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
1Ph High impedance differential
protection
HZPDIF
Id
SYMBOL-CC V2 EN
87
5.2.2
Introduction
The 1Ph High impedance differential protection (HZPDIF, 87) function can be used
when the involved CTs have the same turns ratio and similar magnetizing
characteristics. It utilizes an external CT current summation by wiring, a series resistor,
and a voltage dependent resistor which are mounted externally connected to the IED.
HZPDIF (87) can be used to protect tee-feeders or busbars. Six single phase function
blocks are available to allow application for two three-phase zones busbar protection.
1MRK505222-UUS C
Section 5
Differential protection
161
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...