Table 121:
ZMHPDIS (21) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
OffsetMhoDir
Non-directional
Forward
Reverse
-
-
Non-directional
Direction mode for offset mho
OpModetPG
Disabled
Enabled
-
-
Enabled
Operation mode Disable/ Enable of Zone
timer, Ph-G
OpModetPP
Disabled
Enabled
-
-
Enabled
Operation mode Off / On of Zone timer, Ph-ph
6.4.6
Technical data
Table 122:
ZMHPDIS (21) technical data
Function
Range or value
Accuracy
Number of zones with selectable
directions
Max 5 with selectable direction -
Minimum operate current
(10–30)% of I
Base
-
Positive sequence impedance,
phase-to-ground loop
(0.005–3000.000)
W
/phase
± 2.0% static accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: 85 degrees
Positive sequence impedance
angle, phase-to-ground loop
(10–90) degrees
Reverse reach, phase-to-ground
loop (Magnitude)
(0.005–3000.000) Ω/phase
Magnitude of ground return
compensation factor KN
(0.00–3.00)
Angle for ground compensation
factor KN
(-180–180) degrees
Dynamic overreach
<5% at 85 degrees measured
with CVT’s and 0.5<SIR<30
-
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
Operate time
20 ms typically (with static
outputs)
-
Reset ratio
105% typically
-
Reset time
30 ms typically
-
Section 6
1MRK505222-UUS C
Impedance protection
260
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...