12.4.12
Position evaluation POS_EVAL
12.4.12.1
Introduction
Position evaluation (POS_EVAL) function converts the input position data signal
POSITION, consisting of value, time and signal status, to binary signals OPENPOS or
CLOSEPOS.
The output signals are used by other functions in the interlocking scheme.
12.4.12.2
Logic diagram
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC08000469-1-en.vsd
Position including quality
Open/close position of
switch device
IEC08000469-1-EN V1 EN
Only the value, open/close, and status is used in this function. Time information is not
used.
Input position (Value)
Signal quality
Output OPENPOS
Output CLOSEPOS
0 (Breaker intermediate)
Good
0
0
1 (Breaker open)
Good
1
0
2 (Breaker closed)
Good
0
1
3 (Breaker faulty)
Good
0
0
Any
Invalid
0
0
Any
Oscillatory
0
0
12.4.12.3
Function block
POS_EVAL
POSITION
OPENPOS
CLOSEPOS
IEC09000079_1_en.vsd
IEC09000079 V1 EN
Figure 377:
POS_EVAL function block
12.4.12.4
Input and output signals
Table 379:
POS_EVAL Input signals
Name
Type
Default
Description
POSITION
INTEGER
0
Position status including quality
1MRK505222-UUS C
Section 12
Control
753
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...