Table 297:
Current selection for CVGAPC function
Set value for the
parameter
CurrentInput
Comment
1
PhaseA
CVGAPC function will measure the phase A current phasor
2
PhaseB
CVGAPC function will measure the phase B current phasor
3
PhaseC
CVGAPC function will measure the phase C current phasor
4
PosSeq
CVGAPC function will measure internally calculated positive sequence
current phasor
5
NegSeq
CVGAPC function will measure internally calculated negative sequence
current phasor
6
3ZeroSeq
CVGAPC function will measure internally calculated zero sequence current
phasor multiplied by factor 3
7
MaxPh
CVGAPC function will measure current phasor of the phase with maximum
magnitude
8
MinPh
CVGAPC function will measure current phasor of the phase with minimum
magnitude
9
UnbalancePh
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the
current phasor of the phase with maximum magnitude and current phasor
of the phase with minimum magnitude. Phase angle will be set to 0° all the
time
10
PhaseA-PhaseB
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase A current phasor and phase B
current phasor (I
A
-I
B
)
11
PhaseB-PhaseC
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase B current phasor and phase C
current phasor (I
B
-I
C
)
12
PhaseC-PhaseA
CVGAPC function will measure the current phasor internally calculated as
the vector difference between the phase C current phasor and phase L1
current phasor ( I
C
-I
A
)
13
MaxPh-Ph
CVGAPC function will measure ph-ph current phasor with the maximum
magnitude
14
MinPh-Ph
CVGAPC function will measure ph-ph current phasor with the minimum
magnitude
15
UnbalancePh-Ph
CVGAPC function will measure magnitude of unbalance current, which is
internally calculated as the algebraic magnitude difference between the ph-
ph current phasor with maximum magnitude and ph-ph current phasor with
minimum magnitude. Phase angle will be set to 0° all the time
The user can select to measure one of the voltage quantities shown in table
:
Section 10
1MRK505222-UUS C
Multipurpose protection
568
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...