The phase-to-phase loop for the faulty phases will be determined if the angle between
the sequence voltages V
2
and V
1
lies within the sector defined according to figure
and the following conditions are fulfilled:
|V
1
|>
V1MinOP
|V
2
|>
V2MinOp
where:
V1MinOP and V2MinOp
are the setting parameters for positive sequence and negative sequence
minimum operate voltages
The positive sequence voltage V
1
If there is a three-phase fault, there will not be any release of the individual phase
signals, even if the general conditions for V
2
and V
1
are fulfilled.
Phase-to-ground and phase-to-phase-to-ground-fault detection
The detection of phase-to-ground and phase-to-phase-to-ground fault (US patent
5390067) is based on two conditions:
1. Angle relationship between V
2
and I
0
2. Angle relationship between V
2
and V
1
The condition 1 determines faulty phase at single phase-to-ground fault by determine
the angle between V
2
and I
0
.
Section 6
1MRK505222-UUS C
Impedance protection
294
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...