Name
Values (Range)
Unit
Step
Default
Description
OverTrigOp02
Disabled
Enabled
-
-
Disabled
Use over level trig for analog cha 2 (on) or
not (off)
OverTrigLe02
0 - 5000
%
1
200
Over trigger level for analog cha 2 in % of signal
Operation03
Disabled
Enabled
-
-
Disabled
Operation On/Off
NomValue03
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 3
UnderTrigOp03
Disabled
Enabled
-
-
Disabled
Use under level trig for analog cha 3 (on) or
not (off)
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog cha 3 in % of
signal
OverTrigOp03
Disabled
Enabled
-
-
Disabled
Use over level trig for analog cha 3 (on) or
not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog cha 3 in % of signal
Operation04
Disabled
Enabled
-
-
Disabled
Operation On/Off
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Disabled
Enabled
-
-
Disabled
Use under level trig for analog cha 4 (on) or
not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog cha 4 in % of
signal
OverTrigOp04
Disabled
Enabled
-
-
Disabled
Use over level trig for analog cha 4 (on) or
not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog cha 4 in % of signal
Operation05
Disabled
Enabled
-
-
Disabled
Operation On/Off
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Disabled
Enabled
-
-
Disabled
Use under level trig for analog cha 5 (on) or
not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog cha 5 in % of
signal
OverTrigOp05
Disabled
Enabled
-
-
Disabled
Use over level trig for analog cha 5 (on) or
not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog cha 5 in % of signal
Operation06
Disabled
Enabled
-
-
Disabled
Operation On/Off
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Disabled
Enabled
-
-
Disabled
Use under level trig for analog cha 6 (on) or
not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog cha 6 in % of
signal
OverTrigOp06
Disabled
Enabled
-
-
Disabled
Use over level trig for analog cha 6 (on) or
not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog cha 6 in % of signal
Table continues on next page
Section 15
1MRK505222-UUS C
Monitoring
962
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...