14.1.5
Setting parameters
Table 493:
SMPPTRC (94) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Enabled
Disable/Enable Operation
Program
3 phase
1p/3p
1p/2p/3p
-
-
1p/3p
Three pole; single or three pole; single, two or
three pole trip
tTripMin
0.000 - 60.000
s
0.001
0.150
Minimum duration of trip output signal
tWaitForPHS
0.020 - 0.500
s
0.001
0.050
Secures 3-pole trip when phase selection
failed
Table 494:
SMPPTRC (94) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
TripLockout
Disabled
Enabled
-
-
Disabled
If TripLockout is set to On, it will activate
output (CLLKOUT) and trip latch. If set to Off
it will activate only CLLKOUT
AutoLock
Disabled
Enabled
-
-
Disabled
If AutoLock is set to On i will activate lockout
from input (SETLKOUT) and trip, If set to Off
it will activate only from SETLKOUT
14.1.6
Technical data
Table 495:
SMPPTRC (94) technical data
Function
Range or value
Accuracy
Trip action
3-ph, 1/3-ph, 1/2/3-ph
-
Minimum trip pulse length
(0.000-60.000) s
± 0.5% ± 10 ms
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
14.2
Trip matrix logic TMAGGIO
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Trip matrix logic
TMAGGIO
-
-
1MRK505222-UUS C
Section 14
Logic
867
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...