1
a g
Re
ABM
AB
V
AngDir
n
AngNeg
s
I
-
<
<
EQUATION2007 V2 EN
(Equation 23)
where:
AngDir
is the setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees) and
AngNegRes is the setting for the upper boundary of the forward directional characteristic, by default set
V1
AM
is positive sequence memorized phase voltage in phase A
I
A
is phase current in phase A
V1
ABM
is memorized voltage difference between phase A and B (B lagging A)
I
AB
is current difference between phase A and B (B lagging A)
The setting of
AngDir
and
AngNegRes
is by default set to 15 (= -15) and 115 degrees
respectively, see figure
, and it should not be changed unless system studies have
shown the necessity.
ZDSRDIR (21D) generates a binary coded signal on the output STDIR depending on
the evaluation where FWD_A=1 adds 1, REV_A=1 adds 2, FWD_B=1 adds 4.
R
X
AngDir
AngNegRes
en05000722_ansi.vsd
ANSI05000722 V1 EN
Figure 93:
Setting angles for discrimination of forward and reverse fault
Section 6
1MRK505222-UUS C
Impedance protection
206
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...