Table 304:
CVGAPC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
MultPU_OC1
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for OC1
ResCrvType_OC1
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for OC1
tResetDef_OC1
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve OC1
P_OC1
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OC1
A_OC1
0.000 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OC1
B_OC1
0.000 - 99.000
-
0.001
0.000
Parameter B for customer programmable
curve for OC1
C_OC1
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OC1
PR_OC1
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for OC1
TR_OC1
0.005 - 600.000
-
0.001
13.500
Parameter TR for customer programmable
curve for OC1
CR_OC1
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for OC1
MultPU_OC2
1.0 - 10.0
-
0.1
2.0
Multiplier for scaling the current setting value
for OC2
ResCrvType_OC2
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Selection of reset curve type for OC2
tResetDef_OC2
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve OC2
P_OC2
0.001 - 10.000
-
0.001
0.020
Parameter P for customer programmable
curve for OC2
A_OC2
0.000 - 999.000
-
0.001
0.140
Parameter A for customer programmable
curve for OC2
B_OC2
0.000 - 99.000
-
0.001
0.000
Parameter B for customer programmable
curve for OC2
C_OC2
0.000 - 1.000
-
0.001
1.000
Parameter C for customer programmable
curve for OC2
PR_OC2
0.005 - 3.000
-
0.001
0.500
Parameter PR for customer programmable
curve for OC2
TR_OC2
0.005 - 600.000
-
0.001
13.500
Parameter TR for customer programmable
curve for OC2
CR_OC2
0.1 - 10.0
-
0.1
1.0
Parameter CR for customer programmable
curve for OC2
tResetDef_UC2
0.00 - 6000.00
s
0.01
0.00
Reset time delay used in IEC Definite Time
curve UC2
Table continues on next page
1MRK505222-UUS C
Section 10
Multipurpose protection
591
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...