Set value:
Mode
Formula used for complex power calculation
C,A
*
C
A
CA
*
S
V
(I
I
)
=
×
-
EQUATION2043 V1 EN
(Equation 112)
A
*
A
A
S 3 V
I
= ×
×
EQUATION2044 V1 EN
(Equation 113)
B
*
B
B
S 3 V
I
= ×
×
EQUATION2045 V1 EN
(Equation 114)
C
*
C
C
S 3 V
I
= ×
×
EQUATION2046 V1 EN
(Equation 115)
The active and reactive power is available from the function and can be used for
monitoring and fault recording.
The component of the complex power S = P + jQ in the direction
Angle1(2)
is
calculated. If this angle is 0° the active power component P is calculated. If this angle
is 90° the reactive power component Q is calculated.
The calculated power component is compared to the power pick up setting
Power1(2)
.
A pickup signal PICKUP1(2) is activated if the calculated power component is larger
than the pick up value. After a set time delay
TripDelay1(2)
a trip TRIP1(2) signal is
activated if the pickup signal is still active. At activation of any of the two stages a
common signal PICKUP will be activated. At trip from any of the two stages also a
common signal TRIP will be activated.
To avoid instability there is a settable hysteresis in the power function. The absolute
hysteresis of the stage1(2) is
Hysteresis1(2)
= abs
(Power1(2)
– drop-power1(2)). For
generator reverse power protection the power setting is very low, normally down to
0.02 p.u. of rated generator power. The hysteresis should therefore be set to a smaller
value. The drop-power value of stage1 can be calculated with the
Power1(2)
,
Hysteresis1(2)
: drop-power1(2) =
Power1(2)
–
Hysteresis1(2)
For small power1 values the hysteresis1 may not be too big, because the drop-
power1(2) would be too small. In such cases, the hysteresis1 greater than (0.5 ·
Power1(2)
) is corrected to the minimal value.
If the measured power drops under the drop-power1(2) value the function will reset
after a set time
DropDelay1(2)
. The reset means that the pickup signal will drop out ant
that the timer of the stage will reset.
1MRK505222-UUS C
Section 7
Current protection
481
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...