Name
Values (Range)
Unit
Step
Default
Description
IMinPUPG
5 - 30
%IB
1
5
Minimum pickup phase current for Phase-to-
ground loops
AngNegRes
90 - 175
Deg
1
115
Angle of blinder in second quadrant for
forward direction
AngDir
5 - 45
Deg
1
15
Angle of blinder in fourth quadrant for forward
direction
6.9.6
Technical data
Table 155:
ZMRPDIS, ZMRAPDIS (21) technical data
Function
Range or value
Accuracy
Number of zones
Max 5 with selectable
direction
-
Minimum operate residual
current, zone 1
(5-1000)% of IBase
-
Minimum operate current, phase-
to-phase and phase-to-ground
(10-1000)% of IBase
-
Positive sequence reactance
(0.10-3000.00) Ω/
phase
± 2.0% static accuracy
± 2.0 degrees static angular accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Angle: at 0 degrees and 85 degrees
Positive sequence resistance
(0.01-1000.00) Ω/
phase
Zero sequence reactance
(0.10-9000.00) Ω/
phase
Zero sequence resistance
(0.01-3000.00) Ω/
phase
Fault resistance, phase-to-
ground
(0.10-9000.00) Ω/loop
Fault resistance, phase-to-phase (0.10-3000.00) Ω/loop
Dynamic overreach
<5% at 85 degrees
measured with CVT’s
and 0.5<SIR<30
-
Impedance zone timers
(0.000-60.000) s
± 0.5% ± 10 ms
Operate time
24 ms typically
-
Reset ratio
105% typically
-
Reset time
30 ms typically
-
1MRK505222-UUS C
Section 6
Impedance protection
325
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...