17.9.6
Setting parameters
Table 675:
MULTICMDRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tMaxCycleTime
0.050 - 200.000
s
0.001
11.000
Maximum cycle time between receptions of
input data
tMinCycleTime
0.000 - 200.000
s
0.001
0.000
Minimum cycle time between receptions of
input data
Mode
Steady
Pulsed
-
-
Steady
Mode for output signals
tPulseTime
0.000 - 60.000
s
0.001
0.200
Pulse length for multi command outputs
Table 676:
MULTICMDSND Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
tMaxCycleTime
0.000 - 200.000
s
0.001
5.000
Maximum time interval between transmission
of output data
tMinCycleTime
0.000 - 200.000
s
0.001
0.000
Minimum time interval between transmission
of output data