Function
Range or value
Accuracy
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 10 x I
set
-
Reset time
35 ms typically at 10 to 0 x I
set
-
Critical impulse time
2 ms typically at 0 to 10 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
7.4
Four step residual overcurrent protection, zero,
negative sequence direction EF4PTOC (51N/67N)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Four step residual overcurrent
protection
EF4PTOC
4
4
alt
IN
TEF-REVA V1 EN
51N/67N
7.4.1
Introduction
The four step residual overcurrent protection EF4PTOC (51N/67N) has an inverse or
definite time delay independent for each step separately.
All IEC and ANSI time-delayed characteristics are available together with an optional
user defined characteristic.
EF4PTOC (51N/67N) can be set directional or non-directional independently for each
of the steps.
IDir, VPol and IPol can be independently selected to be either zero sequence or
negative sequence.
Second harmonic blocking can be set individually for each step.
EF4PTOC (51N/67N) can be used as main protection for phase-to-ground faults.
EF4PTOC (51N/67N) can also be used to provide a system back-up for example, in the
case of the primary protection being out of service due to communication or voltage
transformer circuit failure.
1MRK505222-UUS C
Section 7
Current protection
399
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...