NS4PTOC (4612) can be completely blocked from the binary input BLOCK. The
pickup signals from NS4PTOC (4612) for each stage can be blocked from the binary
input BLKx. The trip signals from NS4PTOC (4612) can be blocked from the binary
input BLKTR.
7.5.2.7
Directional supervision element with integrated directional comparison
function
At least one of the four negative sequence overcurrent steps must be set
as directional in order to enable execution of the directional supervision
element and the integrated directional comparison function.
NS4PTOC (4612) has integrated directional feature. As the operating quantity current
Iop is always used. The polarizing method is determined by the setting
polMethod
. The
polarizing quantity can be selected by NS4PTOC (4612) in one of the following two
ways:
•
When
polMethod
=
Voltage
, VVPol is used as polarizing quantity
•
When
polMethod
=
Dual
, VTotPol is used as polarizing quantity
The operating and polarizing quantity are then used inside the directional element, as
shown in figure
, to determine the direction of the fault.
Section 7
1MRK505222-UUS C
Current protection
426
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...