By choosing
CBReadyType = CO
(CB ready for a Close-Open sequence) the readiness
of the circuit breaker is also checked before issuing the CB closing command. If the
CB has a readiness contact of type
CBReadyType = OCO
(CB ready for an Open-Close-
Open sequence) this condition may not be complied with after the tripping and at the
moment of reclosure. The Open-Close-Open condition was however checked at the
start of the reclosing cycle and it is then likely that the CB is prepared for a Close-
Open sequence.
The synchronism check or energizing check must be fulfilled within a set time interval,
tSync
. If it is not, or if other conditions are not met, the reclosing is interrupted and
blocked.
The reset timer defines a time from the issue of the reclosing command, after which the
reclosing function resets. Should a new trip occur during this time, it is treated as a
continuation of the first fault. The reset timer is started when the CB closing command
is given.
A number of outputs for Autoreclosing state control keeps track of the actual state in
the reclosing sequence.
Section 12
1MRK505222-UUS C
Control
638
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...