6.11
Power swing detection ZMRPSB (68)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Power swing detection
ZMRPSB
Zpsb
SYMBOL-EE V1 EN
68
6.11.1
Introduction
Power swings may occur after disconnection of heavy loads or trip of big generation
plants.
Power swing detection function (ZMRPSB, 68) is used to detect power swings and
initiate block of selected distance protection zones. Occurrence of ground-fault
currents during a power swing inhibits the ZMRPSB (68) function to allow fault
clearance.
6.11.2
Principle of operation
Power swing detection (ZMRPSB ,68) function comprises an inner and an outer
quadrilateral measurement characteristic with load encroachment, as shown in
figure
Its principle of operation is based on the measurement of the time it takes for a power
swing transient impedance to pass through the impedance area between the outer and
the inner characteristics. Power swings are identified by transition times longer than a
transition time set on corresponding timers. The impedance measuring principle is the
same as that used for the distance protection zones. The impedance and the
characteristic passing times are measured in all three phases separately.
One-out-of-three or two-out-of-three operating modes can be selected according to the
specific system operating conditions.
1MRK505222-UUS C
Section 6
Impedance protection
347
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...