7.1.5
Setting parameters
Table 186:
PHPIOC (50) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Disable/Enable Operation
IBase
1 - 99999
A
1
3000
Base current
OpModeSel
2 out of 3
1 out of 3
-
-
1 out of 3
Select operation mode (2 of 3 / 1 of 3)
Pickup
1 - 2500
%IB
1
200
Phase current pickup in % of IBase
Table 187:
PHPIOC (50) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
MultPU
0.5 - 5.0
-
0.1
1.0
Multiplier for operate current level
7.1.6
Technical data
Table 188:
PHPIOC (50) technical data
Function
Range or value
Accuracy
Operate current
(1-2500)% of lBase
±
1.0% of I
n
at I
£
I
n
±
1.0% of I at I > I
n
Reset ratio
> 95%
-
Operate time
25 ms typically at 0 to 2 x I
set
-
Reset time
25 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 10 x I
set
-
Reset time
35 ms typically at 10 to 0 x I
set
-
Critical impulse time
2 ms typically at 0 to 10 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
7.2
Four step phase overcurrent protection OC4PTOC
(51/67)
1MRK505222-UUS C
Section 7
Current protection
381
Technical reference manual
Summary of Contents for Relion 670 series
Page 1: ...Relion 670 series Line differential protection RED670 ANSI Technical reference manual...
Page 2: ......
Page 40: ...34...
Page 50: ...44...
Page 60: ...54...
Page 126: ...120...
Page 384: ...378...
Page 496: ...490...
Page 556: ...550...
Page 602: ...596...
Page 620: ...614...
Page 794: ...788...
Page 864: ...858...
Page 988: ...982...
Page 998: ...992...
Page 1084: ...1078...
Page 1164: ...1158...
Page 1168: ...1162...
Page 1220: ...1214...
Page 1230: ...1224...
Page 1231: ...1225...