214/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.191 Release of heat pump above the outside
temperature threshold
•
Outside temperature for release of the heat pump can be defined
Definition of the outside temperature
above
which the heat pump may be put into op-
eration.
Setting range
Unit
Factory setting
--- / -30...30
°C
- - -
---
Heat pump is always released
The heat pump is released when the composite outside temperature lies above the
adjusted value. The heat pump is locked when the outside temperature lies below the
adjusted value.
The switching points for release and locking are separated by a switching differential to
absorb small outside temperature variations.
Refer to “Release of outside temperature” (above operating line 630).
4.192 Release of wood-fired boiler below the
outside temperature threshold
•
Outside temperature for release of the wood-fired boiler can be defined
Definition of the outside temperature
below
which the wood-fired boiler may be put into
operation.
Setting range
Unit
Factory setting
--- / -30...30
°C
- - -
---
Wood-fired boiler is always released
The wood-fired boiler is released when the composite outside temperature lies below
the adjusted value. The wood-fired boiler is locked when the outside temperature lies
above the adjusted value.
The switching points for release and locking are separated by a switching differential to
absorb small outside temperature variations.
Refer to “Release of outside temperature” (above operating line 630).