Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.170 Minimum d.h.w. storage tank temperature
level when charging with the collector
(TBmin)
Charging of the d.h.w. storage tank via solar collectors (B6 / B61) is accomplished via
the temperature differentials ON and OFF against the actual value of the d.h.w. storage
tank (TBx) at the relevant heat exchanger.
In the case of
stratification storage tanks,
the “Minimum d.h.w. storage tank tem-
perature level when charging with collector” (TBmin) can be used as an additional
switch-on criterion.
In that case, the ON / OFF temperature differential against the higher of the 2 values
(TBx or TBmin) is to be maintained.
Setting range
Unit
Factory setting
0…(line 523)
°C
80
This ensures that the upper part of the stratification storage tank (possible with Sol 4, 9,
10, 11 and 15) will be raised to a higher temperature level already at the beginning of
charging instead of heating the storage tank evenly but at a much lower temperature
level.
23
92Z
51
B6 / B61
ON
OFF
Q5
Q16
K8
K12
°C
TBx
t
t
329 / 331
Temperature differential ON heat exchanger 1 / 2
330 / 332
Temperature differential OFF heat exchanger 1 / 2
B6/B61
Collector temperature 1 / 2
TBx
Actual value of the d.h.w. storage tank temperature
Q5/Q16/K12 Collector
pumps
K8
Collector pump or diverting valve
Description
Setting
Effect
Example