334/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Technical data
04.11.2009
8 Technical
data
Nominal voltage
AC 230 V (+10 % / –15 %)
Nominal frequency
50 Hz (±6 %)
Power consumption
max. 10 VA
conformity to
EMC directive
2004/108/EC
Immunity and emissions
EN 60730-1 (for use in industrial and
domestic environments)
Low voltage directive
2006/95/EC
Safety
EN 60730-1 / EN 60730-2-9
Degree of protection
IP40 to EN 60529 (when correctly
installed)
Safety class
II to EN 60730
Operation to IEC 721-3-3
class 3K5 (non-condensing)
Temperature 0…50
°C
Storage to IEC 721-3-1
class 1K3 –25…70 °C
Transport to IEC 721-3-2
class 2K3 –25…70 °C
To EN 60 730
usual environment
Operation to IEC 721-3-3
class 3M2
Storage to IEC 721-3-1
class 1M2
Transport to IEC 721-3-2
class 2M2
To EN 60 730 par. 11.4
1b
Voltage range
AC 24…230 V
Nominal current Q101
AC 0.02…2 (2) A
Nominal current Q102…Q110
AC 0.02…1 (1) A
Nominal current ignition transformer
max. 1 A during max. 30 s
Switch-on current ignition transformer
max. 10 A during max.10 ms
To sensors and external contacts
(copper cable, 2 wires, interchangeable)
0.6 mm
2
20 m
1.0 mm
2
80 m
1.5 mm
2
120 m
To the room unit (PPS)
(copper cable, 2 wires, interchangeable)
0.25 mm
2
25 m
0.5 mm
2
50 m
Cable length for LPB:
(copper cable 1.5 mm
2
, 2-wire
not
interchangeable)
With controller bus power supply
(per controller)
250 m
With central bus power supply
460 m
Bus loading number
E = 3
Power supply
Requirements
Climatic
conditions
Contamination
Mechanical
conditions
Mode of operation
Output relays
Perm. cable lengths