Line Function
Range
Unit
Resolution Factory
setting
Hours run counter
311 Number of operating hours collector pump 1 (output Q5)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
312 Number of operating hours collector pump 2 (output Q16)
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
313 Number of operating hours pump K12
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
314 Number of operating hours diverting valve K8
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
315 Number of operating hours swimming pool heating K18
To reset to 0, press the + / - buttons simultaneously for 3 seconds
0...999‘999 h
1
0
Swimming pool heating
317 Setpoint temperature swimming pool
0…line 321
°C
1
25
318 Actual value of swimming pool temperature B13
--- No
value
available
–50...350 °C 1 –
319 Temperature differential swimming pool ON
Line 320…40
K
1
8
320 Temperature differential swimming pool OFF
0…line 319
K
1
4
321 Maximum swimming pool charging temperature
20...95
°C
1
35
322 Heat exchanger-pump operation for swimming pool
1 Alternatively
2 Parallel
1 / 2
–
1
1
323 Measured value correction swimming pool sensor B13
-10.0...10.0
K
0.1
0.0
Functions
324 Selection of type of collector sensor B6 / B61
1 LG-Ni
1000
2 Pt
1000
1...2 –
1
1
325 Measured value correction collector sensor B6
-10.0...10.0
K
0.1
0.0
326 Measured value correction collector sensor B61
-10.0...10.0
K
0.1
0.0
327 Measured value correction collector flow sensor B62
-10.0...10.0
K
0.1
0
328 Heat exchanger pump operation for partial diagram Sol 5
1 Alternative
operation
2 Parallel
operation
1...2 –
1
2
329 Temperature differential ON heat exchanger 1
Line 330…40
°C
1
8
330 Temperature differential OFF heat exchanger 1
0…line 329
°C
1
4
331 Temperature differential ON heat exchanger 2
Line 332…40
°C
1
8
332 Temperature differential OFF heat exchanger 2
0…line 331
°C
1
4
333 Priority with 2 heat exchangers
1 No
priority
2
Rel. priority buffer storage tank (heat exchanger 1)
3
Abs. priority buffer storage tank (heat exchanger 1)
4
Rel. priority d.h.w. storage tank (heat exchanger 2)
5
Abs. priority d.h.w. storage tank (heat exchanger 2)
1...5 –
1
4
Solar yield / discharge measurement
338 Type of antifreeze agent
1
None (only water)
2 Ethylenglykol
3 Propylenglykol
4
Mixture of Ethylen and Propylenglykol
1...4 –
1
1
339 Concentration of antifreeze agent
1...100
%
1
30
340 Pulse value of flow measurement
Supported 1, 2.5, 10, 25, 100 liters / pulse
1.0 / 2.5 / 10 /
25 / 100
– –
10.0
341 Volumetric flow solar pump
10...1500
Liters / h
1
200
342 Selection of type of sensor for solar yield measurement
(B63 and B64)
1 LG-Ni
1000
2 Pt
1000
1 / 2
–
1
2
343 Actual value of solar flow temperature B63
--- No
value
available
–50...350 °C 1 –
344 Actual value of solar return temperature B64
--- No
value
available
–50...350 °C 1 –