76/348
Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
3.25 Preselection of holiday periods
•
Several holiday periods per year can be selected
Display
Unit
1...8 -
3.26 Start and end of the holiday period
•
The dates of the individual holiday periods can be set
Display
Unit
--.-- / 01.01...31.12
Day.Month
---
Holiday period inactive
To set the holiday program to “inactive”, press the + / - buttons simultaneously for 3
seconds.
General / service
3.27 Indication of faults
•
Straightforward
checking
of
plant
•
Fault tracing is made easier
The controller indicates errors that can occur in the controller itself or in the system.
The display shows "Er" when an error has occurred.
Display
Unit
0...255 -
The first entry in the error list will automatically be displayed on this operating line. By
pressing
, it is possible to switch between the error messages.
The controller can store a maximum of 10 error messages. The error signal will be
cleared only after the cause of the error has been removed. If additional errors are pre-
sent, they will be stored when storage capacity becomes available. Errors are displayed
in the order of their priority, that is, an error with priority 9 is displayed before an error
with priority 6, for example.
Errors occurring on this operating line (priority 5 and higher) can be passed on or visu-
alized by means of the alarm output (refer to auxiliary function ”Alarm output”, operating
line 151). The alarm output can be reset by pressing the + / - buttons simultaneously for
3 seconds (operating line 50). But the error in the error list remains.
Benefit
Setting
Benefit
Settings
Note
Benefit
Description
Setting
Effect
Error messages
Note