Siemens Building Technologies
Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the enduser settings
18.10.2002
3.2 Operating mode of d.h.w. heating
•
Selection of d.h.w. heating mode independent of heating operation
•
Selection is made directly on the user interface
D.h.w. heating can be switched on and off independent of the heating circuit operating
modes.
D.h.w. heating is selected by pressing the respective button on the controller's user in-
terface.
By pressing the respective button, d.h.w. heating is switched on or off.
•
D.h.w.
heating
OFF
- button dark.
D.h.w. is not being heated. Frost protection remains active, however, and prevents
the storage tank temperature from falling below a certain level.
•
D.h.w.
heating
ON
- button illuminated.
The d.h.w. is heated according to the settings made.
The following settings affect d.h.w. heating:
Time switch program d.h.w. heating (operating lines 19...25)
Nominal d.h.w. temperature setpoint (operating line 26)
Reduced d.h.w. temperature setpoint (operating line 770)
Release of d.h.w. heating (operating line 771)
Assignment of d.h.w. heating (operating line 773)
D.h.w. heating (operating line 774)
Type of d.h.w. demand (operating line 775)
Green button (operating line 801)
When the wood-fired boiler or the solar collector can deliver heat, the d.h.w. can be
heated independent of the current d.h.w. operating mode (that is, even if there is no
demand for heat from d.h.w.).
The frost protection temperature for d.h.w. is fixed at 5 °C and always active.
3.2.1 Manual d.h.w. push
In terms of function, the manual d.h.w. push is identical with the automatic d.h.w. push
(refer to operating line 779), the only difference being manual triggering.
The manual d.h.w. push is triggered by pressing the d.h.w. operating mode button for
more than 3 seconds. As a confirmation, the d.h.w. LED flashes briefly.
Benefit
Description
Setting
Effect
Important settings
Notes