Description of the heating engineer settings
18.10.2002
4.102 Maximum speed of the solar pump
•
Maximum limitation of speed of solar pump Q5 / K9
The maximum speed of the solar pump can be defined. It is thus possible to negate the
highest pump speeds, if required.
Setting range
Unit
Factory setting
Line 346…100
%
100
Diagnosis
4.103 Functional test solar
•
Individual relays or combinations of relays can be controlled for test purposes
To check the functionality, the functional test enables individual terminals or combina-
tions of terminals to be controlled.
Setting range
Unit
Factory setting
--- / 0...4
–
---
The following test steps are available (to activate the required test step, use the + / -
buttons):
--- No
test
0 Everything
OFF
1 Q5/K12
ON
2 Q5/K12
+
Q16
ON
3
Q5/K12 + Q16 + K9 ON
4
Q5/K12 + Q16 +K9 + K8 ON
The functional test will be terminated when quitting the operating line.