Basic Documentation RVP540 / RVP550
CE1P2488en
HVAC Products
Description of the heating engineer settings
18.10.2002
4.90 Temperature differential OFF heat exchanger
•
Switching differential can be selected depending on the requirements
Temperature differential (
Δ
T) between storage tank and collector sensor for switching
off the relevant heat exchanger.
Setting range
Unit
Factory setting
0…line 329
0…line 331
°C
°C
4
4
Temperature differential OFF heat exchanger 1
Temperature differential OFF heat exchanger 2
The switching differential defines the temperature differential
Δ
T between storage tank
and collector sensor (B6 or B61) at which storage tank charging via the respective heat
exchanger will be stopped.
When the temperature differential drops below that level, the pumps will be deactivated.
The type of storage tank sensor used for generating the temperature differentials is de-
pendent on the selected basic diagram. The assignment of the sensors to the heat ex-
changers is described on page 143.
2392Z47
TSx
K12 / K8
ON
OFF
/
/
K12
Pump of heat exchanger 1
K8
Pump of heat exchanger 2
TSx
Actual value of the solar collector temperature
when the storage tank temperature is constant
Benefit
Description
Setting
Effect
Note